Rising Temperatures Force Rethink of Cold-Water Plumbing as Flushing Strategies Fail
Rising summer temperatures are forcing a fundamental rethink of cold-water plumbing design in Germany as conventional flushing strategies fail to keep drinking water cool and safe, SBZ Online reported.
Planners can no longer rely on high-volume flushing to maintain hygiene in cold-water systems because rising temperatures push pipe networks above the 25 °C safety threshold, according to the report. The volumes required now strain municipal supply limits during heat waves, and the water is wasted. “With increasing building entry temperatures and rising indoor temperatures during longer high-temperature phases, the water volumes required for this have increased sharply,” the report says. “At the same time, precipitation often fails to occur during these phases, which has a negative effect on water availability.” The technical rules governing installations — DIN 1988-200, DIN EN 806-5, VDI 6023 and the Drinking Water Ordinance — are fragmented and sometimes contradictory, leaving engineers to reconcile competing targets for hygiene, conservation and cost, according to Sbz Online. DIN 1988-200 Section 3.2.2 requires both avoidance of water waste and sufficient water exchange during intended operation. Four factors determine whether a system stays hygienic: flow-through, temperature, water exchange and nutrient supply from pipe materials. They interact and must be planned together. On temperature, the goal is to avoid the critical 25–50 °C range where microbes multiply. Passive measures — such as the selection of suitable installation areas — remain a factor.
When those are not enough, active cooling and cold-water circulation (PWC-C) are gaining importance. The report cites the CoolFlow system as an example that can hold circulating water at ≤ 20 °C continuously, eliminating the need for temperature-control flushing and cutting operating costs. On water exchange, the standards differ: DIN EN 806-5 sets a seven-day requirement, VDI 6023 Part 1 recommends 72 hours, and some engineers argue for 24 hours depending on water quality, materials and temperature. The report says the specialist must decide and document the choice in the operating instructions. Ring installations with flow dividers outperform conventional T-piece or series layouts.
An investigation at the Fachbereich Energie-Gebäude-Umwelt found that cold water in a ring system with flow dividers stayed below 20 °C for almost 17 hours a day, while conventional layouts exceeded 25 °C for 14 hours and dipped below 20 °C for only about two hours.
Where flushing cannot be avoided, the report argues for using flushing water instead of wasting it. This reduces operating costs and conserves the drinking water resource. “A responsible approach to drinking water means: every liter that does not flow away unused or is wasted for non-drinking purposes is a step in the right direction,” the report concludes.