NASA Analysis Finds Optimal Power Source for Orbital Data Centers Varies
A new analysis from NASA finds that the optimal power source for future space data centers depends on mission requirements.
According to a paper by Dr. Slava Turyshev of NASA’s Jet Propulsion Laboratory, the choice between solar, nuclear, or a hybrid system for orbital data centers hinges on trade-offs between weight, cost, and mission needs. Solar power faces a significant mass penalty due to Earth’s shadow, while nuclear power introduces its own engineering and radiation challenges.
Battery Burden for Solar Power
A major problem with solar panels is the intermittent sunlight. During some seasons, satellites in low orbit pass through Earth’s shadow for up to 21 minutes per orbit. With about 15 orbits per day, a satellite spends roughly 5 hours and 13 minutes in darkness each 24-hour period, phys.org and universetoday.com reported.
To bridge these power gaps, engineers use batteries. Turyshev’s calculations show that providing enough battery storage for a 1-megawatt data center to survive a 21-minute outage would require hauling 6.46 metric tons of batteries into orbit. Combined with solar panels and radiators for waste heat, a fully solar-powered 1 MW cluster would reach 43 metric tons before including any computing hardware, phys.org and universetoday.com reported.
Fission Reactor Sheds Weight Produces Waste Heat
A nuclear fission reactor eliminates the need for solar wings and batteries, offering a potential weight advantage. A compact fission reactor weighs about 10 metric tons less per megawatt than today’s standard solar panels, everythingspace.online reported.

However, reactors introduce a different challenge: waste heat. Running a reactor at 25% efficiency produces about 3 megawatts of waste heat for every 1 megawatt of power generated. This heat, at around 700 kelvins, must be radiated away separately from the cooling needed for the processors, which must stay below 320 kelvins, phys.org reported. Despite the different temperatures, a nuclear-powered cluster only requires about 6% less low-temperature radiator area than a solar-powered one.
Nuclear power also carries a radiation risk. Data centers in space are sensitive to radiation, and a reactor’s gamma rays and neutrons can interfere with hardware. Shielding the reactor or placing it on a long boom to separate it from the servers adds weight, eroding some of the initial advantage, phys.org reported.
Reactor End-of-Life Disposal
A nuclear-powered satellite cannot simply burn up in the atmosphere at the end of its operational life. The spent reactor must be actively boosted to a “graveyard” orbit at approximately 2,000 km (1,240 miles), where it will remain indefinitely, according to the analysis.
This disposal requirement adds a final layer of complexity to the mission architecture, creating a long-term management challenge that is not a concern for solar-powered satellites, which are designed to deorbit and safely re-enter Earth’s atmosphere.
Mission Architecture Backing
A new analysis from JPL researcher Slava Turyshev examines whether future orbital data centers should be powered by solar panels, nuclear fission reactors, or a mix of both, finding that the right choice depends on mission requirements.
Hybrid System Weighs Less Meets Mission Needs
A hybrid system, splitting power 80% nuclear and 20% solar, could be the lightest option for specific missions. According to the analysis, this configuration weighs about 36 metric tons for a 1 MW cluster if the mission requires maintaining 20% emergency power during a full 24-hour system failure. This is about a third of the weight of either standalone system, driven by the reduced battery needs, phys.org reported.
Without that specific power maintenance requirement, either a pure solar or pure nuclear system would be lighter than a hybrid, everythingspace.online noted. The study also highlighted that alternative solutions, like boosting the satellite’s orbit to 1,450 kilometers to avoid Earth’s shadow, could negate the need for heavy batteries, though this introduces other problems like space debris and radiation exposure.
The economics of nuclear power depend on the reactor’s lifespan. If a reactor lasts 10 years, it could save about $190 per kilowatt-year in launch costs compared to solar. However, if it only lasts two years, as some experimental reactors are designed to do, the result is a deficit of $783 per kilowatt-year, phys.org reported. The paper did not address public acceptance of having thousands of nuclear reactors in orbit.